How do I reset a TCSESM ConneXium Ethernet Managed Switch to factory default settings using Hyper Terminal?
Issue
How can a TCSESM ConneXium Ethernet Managed Switch be reset to its factory default configuration using a serial connection?
Important: Resetting the switch to factory defaults erases the existing configuration.
Product Line
- TCSESM ConneXium Ethernet Managed Switch
Environment
The procedure described here uses:
- 490NTRJ11 serial external management cable
- PC with a serial COM port
- HyperTerminal
- Serial communication settings:
- Baud rate: 9600
- Data bits: 8
- Parity: None
- Stop bits: 1
- Flow control: None
Resolution
-
Connect the PC to the TCSESM switch using the 490NTRJ11 serial external management cable.
-
Start HyperTerminal.
- Create a new connection and select the COM port connected to the switch.
-
Configure the COM port as follows:
- 9600 baud
- 8 data bits
- No parity
- 1 stop bit
- No flow control
- Power-cycle the TCSESM switch.
-
During startup, wait for the following message:
"Press <1> to enter System Monitor 1..."
-
Press 1 within approximately 2 seconds.
If the System Monitor is not entered, power-cycle the switch and repeat the procedure.
-
From the System Monitor menu, press 5 to select:
Erase main configuration file
- When prompted to press RETURN to delete the configuration or ESC to cancel, press RETURN.
- Wait for confirmation that the main configuration file has been deleted, then press any key to continue.
-
From the System Monitor menu, press 4 to select:
End (reset and reboot)
-
During the subsequent restart, do not press 1 when the following message appears:
"Press <1> to enter System Monitor 1..."
- Allow the switch to complete its normal startup.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.