Setting up a WRITE_Var command to have a M340 PLC write data over a Serial (Modbus) link.

Article available in these languages:

First in your Unity program open the configuration and double click on the serial port.
M340 serial port

Configure the serial port as needed for your application.
Note: The port must be set to Master for the WRITE_Var to function.

In this example the port is set for RS485, 19200,8,E,1
The Rack, Module, Channel (r.m.c) for the Serial port is always 0.0.0 for a M340 processor

M340 configuation, serial port


Next go to Tools and Project Settings

project settings

In the Project Settings that the last 3 items in the Data types field are checked off.
This will allow us to directly enter Arrays into our project rather than having to first declare them as variables.

options for READ_VAR WRITE _VAR function

Next add a ADDM block to your program, link the OUT pin to the ADR pin of the Read_Var block, and enter the appropriate String to the IN pin.
For Modbus communication the syntax for the IN pin of the ADDM block uses the form r.m.c.e where:
r = rack
m = module
c = channel
e = equipment

The equipment is the slave Modbus address.
Remember that this input is a String so you need ' before and after the text.

Next configure the remaining parameters of the WRITE_Var where:

OBJ = String declaring the type of object to read (%MW or %M)
NUM = The starting register address in the slave TCP/IP device of the object type
NB = The # of registers to read
RECP = Array of length NB where the data to be written is stored.
GEST = Array of length 4 where the Management Exchange table for the WRITE_Var is located

Note: The Array's are of type INT if declared as variables.
example of modbus write_var communication

This example will write 5 registers from %MW10-14 to %MW101-105 in a slave at Modbus address 15

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.