What type of 10Base-FL Fiber is Required for devices with fiber optic communications?
Issue
What is the best type of 10Base-FL Fiber for 10Base-FL communications
Product Line
ION Devices
Environment
Fiber Optic Communications
Cause
Some devices such as older (pre 2008) models of the ION7650 have a fiber-optic communication hardware ordering option
Resolution
These are the best specifications for the the fiber to be on the 10Base-FL port
* Multi-Mode fiber
* Wavelength: 850 nm
* Connector Type: ST
* Cladding: 62.5/125 um
* Max Length: 2000m
Note: For 100Base-FX communications see What type of 100Base-FX Fiber is Required for devices with fiber optic communications?
What is the best type of 10Base-FL Fiber for 10Base-FL communications
Product Line
ION Devices
Environment
Fiber Optic Communications
Cause
Some devices such as older (pre 2008) models of the ION7650 have a fiber-optic communication hardware ordering option
Resolution
These are the best specifications for the the fiber to be on the 10Base-FL port
* Multi-Mode fiber
* Wavelength: 850 nm
* Connector Type: ST
* Cladding: 62.5/125 um
* Max Length: 2000m
Note: For 100Base-FX communications see What type of 100Base-FX Fiber is Required for devices with fiber optic communications?
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.