How can we help you today?
Why does the ATV212 display a flashing StOP when changing from utility to generator power?
Issue:
ATV212 flashing StOP when changing from utility to generator power
Product Line:
ATV21, ATV212
Environment:
All models and serial numbers.
Cause:
Momentary power loss removes output power to motor.
Resolution:
When F302, supply loss behavior, is activated, then a brief loss of input power will cause the drive to remove power from the motor and display the flashing StOP alarm. To restart operation, remove and reapply a new run command signal. To deactivate this function and attempt to ride through the momentary loss of power, set F302 back to the factory default of 0.
ATV212 flashing StOP when changing from utility to generator power
Product Line:
ATV21, ATV212
Environment:
All models and serial numbers.
Cause:
Momentary power loss removes output power to motor.
Resolution:
When F302, supply loss behavior, is activated, then a brief loss of input power will cause the drive to remove power from the motor and display the flashing StOP alarm. To restart operation, remove and reapply a new run command signal. To deactivate this function and attempt to ride through the momentary loss of power, set F302 back to the factory default of 0.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.