How can we help you today?

Why the vfd will not ramp to the correct speed of the 0-10V signal on AI1?


Issue:
The analog input signal do not match what is being sent.

Product line:
Altivar 61/71

Environment:
All models, all serial numbers

Cause:
The AI1 input is a bipolar input.  If AI1 negative is not referenced to common the drive is looking for a range of 20 V dc ( +10 to  - 10).

Resolution:
Verify the factory installed jumper between AI1- and common terminals is installed.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.