Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How do I send a fault reset over Modbus to the ATS48?

Issue:
The ATS48 Fault Reset sent over Modbus.

Product Line:
Altistart 48

Environment:
All models and serial numbers.

Cause:
None

Resolution:
Fault reset is performed when bit 7 of command word 400 transitions from 0 to 1.  Write decimal 128 to register 400.  If there is an offset then write decimal 128 to register 401.  Once the reset has been performed write a decimal 0 to the register to reset bit 7 to 0 to allow transition when the next reset is performed.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings