Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does the ATV71 have a function for up and down speed using logic inputs?

Issue:
Controlling motor speed through logic inputs on the ATV71.

Product Line:
Altivar 61, Altivar 71

Environment:
All models and serial numbers.

Cause:
None

Resolution:
The function [+/- Speed] will allow motor speed to be increased or decreased using logic inputs.  The following parameters apply:

NO. MENU SUB-MENU CODEADJUSTDESCRIPTION
1.6COMMAND------------------RFCCh2 activeRef. 2 switching
1.6COMMAND------------------FR2+/- speedReference 2 Channel
1.7APPL FUN+/- SpeedUSPLix+ speed assign.
1.7APPL FUN+/- SpeeddSPLIx- speed assign.
1.7APPL FUNReference SavedStrEEpromFreq. reference stored

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings