How can I use and cable the LO1 logic output of the ATS01?

Article available in these languages:

Output LO1 is an open collector NPN logic output.

The power supply for this output must be provided by an external source (24 VDC, min. 6 V, max. 30 V, max. current 200 mA).

Wiring

  • Connect the +24 VDC terminal on the external power supply to the load (plug-in relay or control relay, for example).
  • Connect the second load terminal to the LO1 terminal on the ATS.
  • Connect the COM terminal on the ATS to the 0 VDC on the external power supply.

LO1 Circuit diagram

Warning
If the load is inductive, use a freewheel diode on the load.