How is the Estimated motor torque value calculated on the ATV212?

Issue:
With the analog signal FnSL set at 7, estimated motor torque, how can you tell what the scaling of the analog output is?

80378765
ATV212, Altivar 212, S-Flex

Environment:
Altivar

Cause:
Customer needs to know what the scaling factors are.

Resolution:
The base torque value is calculated from the drive HP size and setting of parameter F417 (Rated motor Speed or RPM).
The calculation is Motor HP * 5250 / RPM.

For example, a 10HP drive with 1750RPM.  10*5250/1750 = 20lb-ft or torque.
This means that 100% of the estimated torque is 20 lb-ft.
Since the scaling of the analog output when set to torque is 0-250% of the rated motor torque, the analog output will be scaled 0 to 50 lb-ft.

“If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)“

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.