How do you setup a Jog on the ATV12?
Issue:
Needs a jog input for the Altivar 12 drive.
Product Line:
ATV12, Altivar 12
Environment:
All models
Cause:
Using a logic input to Jog the motor.
Resolution:
Assign a Logic input under the Jog function (COnF > FULL > FUn > JOG). Jog can be assigned to L1h, L2h, L3h or L4h. The Jog function is a speed reference of 5Hz with 0.1s ACC and DEC. This value cannot be adjusted. If you need a jog faster than 5Hz, use a Preset Speed.
In order to Jog, the drive needs to have a direction command (Run Forward or Run Reverse input closed).
The Jog function is not compatible with PI Regulator.
Needs a jog input for the Altivar 12 drive.
Product Line:
ATV12, Altivar 12
Environment:
All models
Cause:
Using a logic input to Jog the motor.
Resolution:
Assign a Logic input under the Jog function (COnF > FULL > FUn > JOG). Jog can be assigned to L1h, L2h, L3h or L4h. The Jog function is a speed reference of 5Hz with 0.1s ACC and DEC. This value cannot be adjusted. If you need a jog faster than 5Hz, use a Preset Speed.
In order to Jog, the drive needs to have a direction command (Run Forward or Run Reverse input closed).
The Jog function is not compatible with PI Regulator.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.