How can we help you today?

PME Web Application: Server Error in '/reporter' Application. The log for database 'tempdb' is not available.

Issue:
When a user attempts to open the "Reports" feature in the PME Web Applications they receive the following error.

Server Error in '/reporter' Application.

The log for database 'tempdb' is not available. Check the event log for related error messages. Resolve any errors and restart the database.

Server error screen from reporter application

Product Line:
Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment:
Web Applications "Reports"

Cause:
There is an issue with the availability of the SQL tempdb database.

Resolution:
Restarting the SQL Server services associated with the PME SQL instance will resolve this problem. The instance associated with a PME is usually named "ION" but could have any name.
  1. Open the Windows Services and locate the SQL Server (ION) service. Right-click on this service and select "restart"
  2. If prompted to restart other services as in the screenshot, click "Yes". This will restart the dependent PME services.
Restarting Ion services

After the SQL Server services have been restarted you will no longer encounter the error noted above, when accessing the "Reports" feature within the PME Web Application.

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.