Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
StruxureWare Data Center Expert will not mount to a share using NTLM version 2
Issue:
Backup fails on a Windows share that requires NTLMv2 authentication

Product Line:
InfraStruXure Central
StruxureWare Data Center Expert

Environment:
StruxureWare Central / Data Center Expert any version 7.2.7 and earlier
Windows security.

Cause:
StruxureWare Data Center Expert does not support mounting to shares that require NTLMv2 authentication. It may in some situations allow you to successfully “test mount”, but will not authenticate when attempting a backup or when using this share as a remote repository.

Resolution:

Add a backup location that does not require NTLMv2 authentication. Backing up to a local computer and share using the private network interface may be a successful solution.

StruxureWare DCE 7.3.1 and above now has the option to choose NTLM version 2.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings