What is the pin-out of the RJ45 socket of an ATV31 / 312 / 320 for connection of Modbus, CanOpen and PowerSuite cables
The RJ45 socket of the ATV31/312/320 can be used for connection to the following networks and accessories:
a PLC via a Modbus bus or via a CANopen network
a PC/laptop loaded with SoMove software
The VW3A31101 remote display terminal on the ATV31 drive, and the VW3A1006 or VW3A1007 remote display options for the ATV312 and 320 drives.
The Pin out of the RJ45 socket on these drives are as follows:
Pin no. Designation Comments
RJ45
1 CAN high CAN-H - Signal for CANopen communication
2 CAN low CAN-L - Signal for CANopen communication
3 CAN GND CAN-GND - Signal for CANopen communication
4 D1 Signal for MODBUS communication
5 D0 Signal for MODBUS communication
6 NC Not used
7 10 Volts 10 V voltage supplied by the ATV31/312/320 which can be used to supply the
8 0 Volts converter when connected using PowerSuite / somove software
Important clarification
For Modbus communication, the signals used for the ATV31 /312 / 320 are D1 and D0 only - the other connections are not used.
For CANopen communication, the signals used for the ATV31 / 312 / 320 are CAN-H, CAN-L and CAN-GND - the other connections are not used.
With the VW3A31101/ VW3A1006/7remote display terminal, the signals used are D1 and D0 as well as the power supply.
Caution: Lengths of cables need to be observed as too greater voltage drop in network connections may cause a malfunction.
Released for: Schneider Electric UK
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.