Why can't I transfer an application between the PC and the XBTN or XBTR terminal using the TSXCUSB485?

Context:

  • The objective is to import or export an application to or from one of the following types of XBT terminal: XBTN200, XBTN400, XBTR400, XBTRT500 or XBTRT511.
  • The PC is connected to the XBT terminal via the TSXCUSB485 converter and the XBTZ925(A) cable.
  • The XBTL1000 displays the message "No terminal connected",
  • or Vijeo Designer Lite displays "No terminal connected".
  • The XBT terminal does not display the message "Waiting for transfer" but shows the error message #204 "Connection in progress".


Possible solutions:

  • Disconnect the XBT-Z925(A) cable and reconnect it the other way round, as it has two cable ends which are not symmetrical.
  • The XBT terminal should then display the message "Waiting for transfer".
  • Check that the Uni-Telway driver installed on the PC is definitely assigned to the corresponding COM port on the TSXCUSB485 converter.
  • The rotary selector switch on the TSXCUSB485 cable must be set to 0 or 1.


Note:

  • The position of the "Polarisation" selector switch on the TSXCUSB485 converter is not relevant to communication
  • TSXCUSB485 is Now obsolete.
  • XBT-Z925(A) is Now obsolete.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings