Why can't I transfer an application between the PC and the XBTN or XBTR terminal using the TSXCUSB485?
Context:
- The objective is to import or export an application to or from one of the following types of XBT terminal: XBTN200, XBTN400, XBTR400, XBTRT500 or XBTRT511.
- The PC is connected to the XBT terminal via the TSXCUSB485 converter and the XBTZ925(A) cable.
- The XBTL1000 displays the message "No terminal connected",
- or Vijeo Designer Lite displays "No terminal connected".
- The XBT terminal does not display the message "Waiting for transfer" but shows the error message #204 "Connection in progress".
Possible solutions:
- Disconnect the XBT-Z925(A) cable and reconnect it the other way round, as it has two cable ends which are not symmetrical.
- The XBT terminal should then display the message "Waiting for transfer".
- Check that the Uni-Telway driver installed on the PC is definitely assigned to the corresponding COM port on the TSXCUSB485 converter.
- The rotary selector switch on the TSXCUSB485 cable must be set to 0 or 1.
Note:
- The position of the "Polarisation" selector switch on the TSXCUSB485 converter is not relevant to communication
- TSXCUSB485 is Now obsolete.
- XBT-Z925(A) is Now obsolete.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.