What are the recommended characteristics for a Modbus Jbus RS485 network cable?
The recommended characteristics of the Modbus/Jbus RS-485 network cable are defined as below.
Twisted pair with tinned copper braid shielding. Minimum overlap: 65%.
Gauge: AWG 24.
Characteristic impedance: 120 ohms.
Maximum linear resistance: 100 ohms/km.
Maximum capacitance between conductors: 60 pF/m.
Maximum capacitance between conductors and shielding: 100 pF/m.
Maximum length of network cable: 1200 m.