What are the characteristics of phase unbalance protection of STR22ME and STR43ME motor trip units for NS100 to 630 circuit-breakers
STR22ME and STR43ME electronic motor trip units incorporate protection against phase unbalance (current).

For the STR22ME trip unit: the unit compares the image of the current in the phases with phase 1 which is used as reference. If the unbalance is greater than 40% the trip will take place between 3.5 and 6 seconds.

For the STR43ME trip unit: the trip unit measures the maximum rms values of the currents on the three phases, calculates the average of these values and compares it with the minimum and maximum rms values. If the difference is greater than 30% (with a tolerance of +/- 10%) for more than 4 seconds (tolerance +/- 10%) the trip occurs.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and an expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Centre

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings