How many ASi slaves are managed by the TWDNOI10M3 ASi master module?

The TWDNOI10M3 module is an AS-Interface master module for Twido PLC or Modicon M238 (TM238LFDC24DT•• or TM238LDD24D T or TM238LFAC24DR•• or TM238LD A24DR)

The TWDNOI10M3 module can manage 31 standard address slaves or 62 extended address slaves, regarding the cycle time 5 ms for 31 standard or extended address slaves or10 ms for 62 extended address slaves.

Attached in this FAQ we can find the Hardware Guide.

Note: The Twido range is discontinued and the possible replacement is the Modicon M221. The software to program this new controller is the EcoStruxure Machine Expert Basic also free. The software can automatically be migrated to this new platform but check with our support center your architecture to validate the migration. You can also use our product substitution tool to help you select the replacement for the Twido: Product substitution

Note 2: The ASi is not supported in the M221 range. You should probably check a new architecture with the BMXEIA0100 if you still want to use ASi : BMXEIA0100 - Master module - upto 62 devices on discrete I/O - upto 31 devices on analog I/O | Schneider Electric UK

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.