How can we help you today?
How can I simulate an application on XBTH, XBTP or XBTE with XBTL1000 without PLC?
In order to simulate an application for a Magelis XBT-H , XBT-P or XBT-E using the XBTL1000 without being connected to a PLC we need:
1) Open the Configuration > Dialogue Table
2) Uncheck the "Use Dialogue Table"
3) Click on "OK"
4) Open the Simulation > Simulation Application
5) Enter address 0 when simulation asks you to.
It is now possible to display the page sequences without getting the error code "Cannot write table".
Note:
This platform is discontinued. Please get access to our digital catalog https://digicat.se.com/ or contact our support center for more information about migrations to a newer platform.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.