How can I simulate an application on XBTH, XBTP or XBTE with XBTL1000 without PLC?

In order to simulate an application for a Magelis XBT-H , XBT-P or XBT-E using the XBTL1000 without being connected to a PLC we need:

1) Open the Configuration > Dialogue Table
2) Uncheck the "Use Dialogue Table"
3) Click on "OK"
4) Open the Simulation > Simulation Application
5) Enter address 0 when simulation asks you to.

It is now possible to display the page sequences without getting the error code "Cannot write table".

Note:

This platform is discontinued. Please get access to our digital catalog https://digicat.se.com/ or contact our support center for more information about migrations to a newer platform.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings