How can we help you today?

Video: How do you set stop type to freewheel stop on an ATV21/212 drive?

Article available in these languages:

Issue:
Set stop type to freewheel stop on an ATV21/212 drive.

Product Line:
Altivar 21
Altivar 212

Environment:
Products sold and used in the United States

Cause:
Freewheel stop in ATV21/212

Resolution:
From 0.0
Press Mode and arrow down to F- - -
Press enter
F110 set to 0
F111 set to 56 (freewheel stop input and run combo)
or
if you need to have a separate input to allow freewheel stop you can setup the drive like this.
F----- enter
F110=0
F111= 2
F112= 1 (This will be your freewheel stop input assigned to R)

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.