How can we help you today?

Why Won’t the S-Flex 212 Drive Start When Using Remote Start (Terminals 5–6)?

Article available in these languages:

Resolution:

If the S-Flex 212 drive does not start when closing the remote start contact on terminals 5–6, check the following common causes:

Troubleshooting Steps:

  1. Verify Remote Mode is Active

    • Ensure the drive is in Remote mode.
    • The LOC (Local) LED should be off. Press the LOC/REM button if needed.
  2. Confirm Proper Control Mode and Wiring

    • Make sure the AFC/Bypass switch is set to AFC mode.
    • Verify terminals 5–6 have a dry contact completing the circuit.
    • Ensure the Lower Limit (LL) is set above 0 Hz if no analog speed reference (VIA/VIB) is used.
  3. Check Communication Card Settings (if installed)

    • If a communication card is present, confirm these parameters:
      • CNOD = 0 (Terminal control)
      • FNOD = 1 (VIA) or 2 (VIB)
      • F108 = 48 (Force local always active)
  4. Inspect Wiring Connections

    • Look for loose or incorrect wiring in the control circuit.
  5. Review External Interlocks

    • Check if an end-of-damper circuit or other interlock is preventing the start command.
  6. Consult the Installation Manual

    • Refer to the S-Flex 212 wiring diagrams (manual 30072-451-83B) for correct configuration.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Attachment(s)

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.