Micom S1 studio modbus communication to a Micom relay through a gateway
Issue
Setup communication to a Micom relay using the Modbus communication protocol through a gateway.
Product Line
Micom S1 studio
Micom relay series
Environment
Modbus communications through a gateway
Cause
Micom S1 studio cannot communicate to a Micom series relay through a gateway.
Resolution
1. Micom S1 studio does not have the ability to add a modbus configured micom relay as part of a daisy chained gateway communication system. In order to communicate to a Micom series relay using the modbus communication protocol the front/rear port of the relay must be used.
NOTE: Other modbus communicating softwares can still be used to read device information for the micom relay through a gateway.
Setup communication to a Micom relay using the Modbus communication protocol through a gateway.
Product Line
Micom S1 studio
Micom relay series
Environment
Modbus communications through a gateway
Cause
Micom S1 studio cannot communicate to a Micom series relay through a gateway.
Resolution
1. Micom S1 studio does not have the ability to add a modbus configured micom relay as part of a daisy chained gateway communication system. In order to communicate to a Micom series relay using the modbus communication protocol the front/rear port of the relay must be used.
NOTE: Other modbus communicating softwares can still be used to read device information for the micom relay through a gateway.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.