How to Restore Backup Database from SQL 2005 to SQL 2012
Issue:
When trying to restore a SQL 2005 database in SQL 2012, the Database Restore will give the following error: “The database was backed up on a sever running version 8.002065. That version is incompatible with this server, which is running version 11.00.3000.”
Product Line:
Power Monitoring Expert v7.2.2
Environment:
SQL Server Management Studio
Cause:
It is not possible to restore a SQL 2005 database directly to SQL 2012.
Resolution:
1) Restore the SQL 2005 database backup on a SQL Server 2008 system.
2) Take a backup of the database from the SQL 2008 system.
3) Restore the SQL 2008 database backup on the SQL 2012 system.
When trying to restore a SQL 2005 database in SQL 2012, the Database Restore will give the following error: “The database was backed up on a sever running version 8.002065. That version is incompatible with this server, which is running version 11.00.3000.”
Product Line:
Power Monitoring Expert v7.2.2
Environment:
SQL Server Management Studio
Cause:
It is not possible to restore a SQL 2005 database directly to SQL 2012.
Resolution:
1) Restore the SQL 2005 database backup on a SQL Server 2008 system.
2) Take a backup of the database from the SQL 2008 system.
3) Restore the SQL 2008 database backup on the SQL 2012 system.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.