Issue
A user would like to import XML data into the PME software.
Product Line
Power Monitoring Expert 7.2
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024
Environment
Virtual ION Processor XML Import module
Data has to be numeric (text / string is not a valid format)
Can only be performed in the VIP
Cause
Some third party data is in XML format and this data needs to be imported into PME.
Resolution
The XML Import module is needed to import XML data into PME.
The following example describes a scenario where a user is importing XML data from a file named "Data.xml" that contains the following content:
<?xml version="1.0" encoding="UTF-8"?>
<Meters>
<Meter ID="1">
<kWh>8</kWh>
<kVARh>6</kVARh>
<kVAh>10</kVAh>
</Meter>
<Meter ID="2">
<kWh>20</kWh>
<kVARh>5</kVARh>
<kVAh>22</kVAh>
</Meter>
</Meters>
Create an XML Import module in the VIP and configure the setup registers as:
- URL: Specifies the location of the XML file (C:\Temp\Data.xml).
- xPath Query 1…N: The xPath query is used to retrieve the data from the xml file; each query returns a single, numeric value. The content of this register must match the XML element of the data you want to retrieve:
//Meters/Meter[1]/kVARh/text()
…
//Meters/Meter[2]/kVAh/text()
Once the 'ReadNow' input register is pulsed, the data is read. The following is what the output of XML Import module will look like:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.