How do I install Vijeo Designer Application onto a New Magelis running Windows and Vijeo Designer Runtime from USB Stick

Article available in these languages:

Issue:

How do I install Vijeo Designer Application onto a New Magelis running Windows and Vijeo Designer Runtime from USB Stick

Product Line:

Vijeo Designer, Magelis, Harmony

Resolution:

Make sure you are using a quality USB stick
Vijeo Designer and the Vijeo Designer Runtime must be matching revisions
Format the USB stick - FAT32

In Vijeo Designer - Navigator - Select your target
with the Property Inspector - Select Download - Click the + to expand - Change Download to File System - Change Path to the Drive location of the USB stick

Right click your target - Select Download to (File System)...
[The Project must be saved in order to download a backup to the target. Save project and continue download] Select Yes
After Downloading Complete
Safely Remove USB Mass Storage Device
Remove USB Stick

Install USB Stick on Magelis
Select Start -> All Programs->Schneider Electric->Vijeo Designer->Tools->Vijeo Designer Application Installer
Browse for the .VDA file on the USB Stick
Open
After it is complete

Select Start ->all programs->Schneider Electrci->Vijeo Designer->Vijeo Designer Runtime

Your Application should start running.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.