How can we help you today?
What will cause enclose units not to run the motor in AFC or in Bypass?
Issue:
Enclosed units not to running the motor in AFC or in Bypass.
Product Line:
SFLEX, EFLEX, MFLEX, CPD, MCC, Field Drive, Econoflex, 58M
Environment :
All Enclosed products with Bypass
Cause:
The motor will not run in AFC or in Bypass
Resolution :
1). Check supply fuse primary side of transformer.
2). Check fuse on the secondary side of the transformer
3). Verify the overload is not tripped, (trip and then reset)
4). Verify the AFC/OFF/Bypass switch is getting voltage
5). With factory drawing in hand check the HOA and the AFC/OFF/Bypass circuit.
Enclosed units not to running the motor in AFC or in Bypass.
Product Line:
SFLEX, EFLEX, MFLEX, CPD, MCC, Field Drive, Econoflex, 58M
Environment :
All Enclosed products with Bypass
Cause:
The motor will not run in AFC or in Bypass
Resolution :
1). Check supply fuse primary side of transformer.
2). Check fuse on the secondary side of the transformer
3). Verify the overload is not tripped, (trip and then reset)
4). Verify the AFC/OFF/Bypass switch is getting voltage
5). With factory drawing in hand check the HOA and the AFC/OFF/Bypass circuit.
Released for: Schneider Electric UK
Explore more
Product:
Explore more
Product:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.