Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How can I disconnect the EMC filter (RFI) on an ATV21?
Observation
An installation incorporating an ATV21 drive may experience the following anomalies:
  • The circuit-breaker on the incoming supply trips for non-IT neutral point connections.
  • The insulation control relay detects an initial fault for IT neutral point connections.
Cause
This is a side-effect of EMC filter type protection devices installed to counter the radio interference emitted by a drive.
Solution
If you are using the ATV21 drive on a system with an isolated or impedance earthed neutral, use a permanent insulation monitor which is compatible with non-linear loads.
ATV21 drives with a nominal value of 480 V have built-in radio frequency interference (RFI) filters with earthed capacitors. If you are using the drive on an impedance earthed system, we recommend that  you isolate the RFI filters from earth so as not to shorten their operating life.
Note: In case of three phase 400V, 5.5kW or less model, if you disconnect the capacitor from ground,
set the parameter of carrier frequency f300 to 6kHz with motor cable length 30m or less.
ATV21H 075N4 to U55N4, ATV21H D22N4 to D30N4

Pull the jumper towards the left of the earth terminal as shown below, which will isolate the RFI filters.
ATV21 terminal layout
ATV21H U75N4 to D18N4
Connect the cable to the power terminal at the top left as shown below, which will isolate the filters.
ATV21 TERMINAL LAYOUT 2
By removing these filters you may cause interference on any electronic equipment in the area
General note regarding the ATV range:

The option to disconnect the RFI filter is available for:
Current ranges: ATV212 , ATV12, ATV320,ATV340, ATV600 and ATV900 series
Obsolete ranges:ATV21, ATV28,ATV31,ATV312, ATV38, ATV58 ,ATV61 and ATV71.

Caution: This option is not available for ATV11 drives.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings