How can we help you today?
What is the output voltage from the ATV212 RYA-RYC contact?
Issue:
Needs the output voltage from the ATV212 RYA-RYC contact
Product Line:
Altivar 212 ATV212
Environment:
All
Cause:
Status indication feedback
Resolution:
There is no drive output voltage from the RYA-RYC contact. This is a dry contact.
Specs are as follows:
Minimum switching capacity: 3mA for 24Vdc
Maximum switching capacity:
resistive load 3A for 250Vac or 30Vdc
inductive load 2A for 250Vac or 30Vdc
Maximum response time: 7msec +- 0.5msec
Needs the output voltage from the ATV212 RYA-RYC contact
Product Line:
Altivar 212 ATV212
Environment:
All
Cause:
Status indication feedback
Resolution:
There is no drive output voltage from the RYA-RYC contact. This is a dry contact.
Specs are as follows:
Minimum switching capacity: 3mA for 24Vdc
Maximum switching capacity:
resistive load 3A for 250Vac or 30Vdc
inductive load 2A for 250Vac or 30Vdc
Maximum response time: 7msec +- 0.5msec
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.