How can we help you today?
In Vijeo Designer, what is the XBTF Compatibility option in target property inspector for?
Issue
In Vijeo Designer, what is the XBTF Compatibility option in target property inspector used for?
Product Line
Vijeo Designer
Environment
HMI Configuration Software for Windows
Resolution
The XBTF compatibility option is only intended for users of Vijeo Designer that have migrated from XBTL1000 using the Switch2Vijeo application converter.
The option changes the runtime behavior of the dialog table in order to give the user the exact same behaviors as XBTL1000 in regards to how the HMI writes to the PLC during 1 dialog table cycle.
In XBTL1000, the there is no "Write Queue". What this means is that if there are 10 writes executed very quickly, it is not guaranteed that all 10 values will be written to the PLC.
In Vijeo Designer, we have a "Write Queue" (buffered write requests to a PLC in HMI memory) where by all requested writes are stored and are ensured to be written. So if there are 10 writes executed very quickly, all 10 values are written to the PLC
At Runtime, a large "Write queue" can slow down a process due to communication latency. For this reason, we created the option "XBTF compatibility" to turn off the Write-Queue, specifically for the dialog table only.
Our recommendation is that if you have not converted over from XBTL1000, do not have this property activated.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.