Is there a replacement for Schneider Electric's ATVPOT25K speed potentiometer for Altivar drives?
Issue:
ATVPOT25K speed potentiometer obsolete replacement for Altivar drives
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
Selection of Speed Potentiometer for speed control
Resolution:
Altivar VFD's can use a speed potentiometer from 5K ohms to 10K ohms.
Suggest using one of the following:
For 22mm
Metal - XB4BD912R10K
Plastic - XB5AD912R10K
For 30mm
Metal - 9001K2108
Plastic - 9001SK2108
ATVPOT25K speed potentiometer obsolete replacement for Altivar drives
Product Line:
Altivar Machines
Environment:
All models and serial numbers
Cause:
Selection of Speed Potentiometer for speed control
Resolution:
Altivar VFD's can use a speed potentiometer from 5K ohms to 10K ohms.
Suggest using one of the following:
For 22mm
Metal - XB4BD912R10K
Plastic - XB5AD912R10K
For 30mm
Metal - 9001K2108
Plastic - 9001SK2108
Released for: Schneider Electric UK