Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What are the values of the 1P breaking capacities of GV2P circuit-breakers in IT earthing system?
The values below are the breaking capacities of GV2P circuit-breakers operating on an IT earthing system at 400 V 50 Hz, as demonstrated by pole-by-pole tests carried out in Schneider Electric laboratories:
  • GV2P only
GV2P01 to GV2P07:          0.1 to 2.5 A          Breaking capacity: 25.0 kA
GV2P08:                               2.5 to 4.0 A         Breaking capacity: 12.5 kA
GV2P10 and GV2P14:     4.0 to 10.0 A         Breaking capacity:  8.0 kA
GV2P16 to GV2P20:         9.0 to 18.0 A        Breaking capacity:   6.0 kA
GV2P21 and GV2P32:    17.0 to 32.0 A        Breaking capacity:  4.5 kA

  • GV2P with GV1L3 limiter
GV2P08 to GV2P16:       2.5 to 14.0 A          Breaking capacity: 25.0 kA
GV2P20:                          13.0 to 18.0 A         Breaking capacity:  12.5 kA
GV2P21 to GV2P32:      17.0 to 32.0 A         Breaking capacity:  10.0 kA

  • GV2P with LA9LB920 limiter
GV2P21 to GV2P32:       17.0 to 32.0 A         Breaking capacity: 12.5 kA

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings