How can we help you today?

What will cause the ATV212 not to go into local mode when pressing the LOC/REM button?

Article available in these languages:


Issue:
What will cause the ATV212 not to go into local mode when pressing the LOC/REM button?

Product Line:
ALTIVAR 212, ALTIVAR 21

Environment:
All serial number

Cause:
When pressing the LOC/REM button the drive will not go to LOC mode.

Resolution:
This could possibly be due to parameter F732 (LOC/REM button disabled) being set to 1. If so, set F732 to 0.   However, if the LOC/REM button is not disabled, then it is likely, the keypad is defective, the drive will need to be replaced.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.