Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the I/O scanning health bit address for a M340 NOE module.
Issue:
I/O scanning health bit address for a M340 NOE module.


Product Line:
M340 PLC


Resolution:
If a BMX NOE 01x0 module is configured in rack 0, slot 3, the health bit address would be as follow:

%IW0.3.0.1    device 1 - 15
%IW0.3.0.2    device 16 - 31
%IW0.3.0.3    device 32 - 47
%IW0.3.0.4    device 48 - 64

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings