Advance One Line Crashing with error "Password Encryption Failed - Cipher initialization failed" in the AdvanceOneLine Status log
Issue
Advance One Line crashes without displaying an error message. However, the Advance One Line Status log shows the following error: Password Encryption Failed – Cipher initialization failed
Product Line
Power SCADA Operations 8.2
Power SCADA Operations 9.0
Power Operation 2020
Power Operation 2021
Power Operation 2022
Power Operation 2023
Power Operation 2024
Environment
Starting Runtime
Advance One Line in PowerLogic SCADA
Cause
Running the Computer Configuration multiple times and repeatedly clicking Register can corrupt or invalidate the local encryption configuration used by Advance One Line.
Resolution
Solution 1 — Reset Advance One Line user configuration
- Navigate to: C:\ProgramData\Schneider Electric\PowerSCADA Expert\v7.40\User
- Open the folder corresponding to the project name in use.
- Open advoneline.ini with Notepad.
- Delete all entries except the first line.
- Save the file.
- Restart Advance One Line.
Solution 2 — Regenerate the cipher configuration
- Navigate to: C:\ProgramData\Schneider Electric\PowerSCADA Expert\v7.40\Config
- Rename PowerLogic.Cipher.dll.config to PowerLogic.Cipher_old.dll.config.
- Restart Advance One Line.
Renaming the PowerLogic.Cipher.dll.config file forces the system to regenerate the encryption key for the machine, resolving the cipher initialization failure.
Recommendation
If you are using an older version of Power Operation, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.com
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.