How can we help you today?

What is the maximum energy value a PM5000 will record before the energy value resets to 0?

Issue
PM5000 energy rollover

Product Line
PM5000 Series Meters

Environment
PM5000

Cause
Limit for maximum energy value

Resolution
The energy value is stored in a signed 64 bit integer register (INT64).
Therefore, the PM5000 series meter accumulated energy value will reset after +/- (263 -1) Wh of energy. (Approximately 9.223 x10^18)
(this value can also be gotten by halving the value of a 64 bit register:  +/- [((264) -1) / 2]

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.