How can we help you today?

Connection issues with ComX for Facility Insights

Issue:
The ComX cannot connect to the remote platform

Resolution:
  • If connected via the Ethernet port, confirm there is no proxy presently configured. If a proxy is configured, consult your network administrator.
  • When connected via Ethernet, it is possible your DNS servers are incompatible with the Schneider Electric server. Temporarily try using the Google DNS server, 8.8.8.8. Contact Schneider Electric technical support if the issue persists.
  • Proceed with a ComX test.
  • Save your configuration if needed, then proceed with a factory reset. Load the config file again and attempt to connect to the remote platform.
  • Confirm that ComX has been properly registered in Facility Insights.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.