Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the THD (Total Harmonic Distortion) for the 140ACI03000 module?

We only specify THD for discrete AC input modules. The 140ACI03000 is strictly 1-5VDC or 4-20mA.

This card has no additional filtering capability outside of the built in low pass filter (-3db cutoff @ 15Hz, +-20%).

If the signal is simply too noisy and can not be cleaned up before it gets to the module, you can try creating some sampling or averaging logic.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings