Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can I Start and Stop the motor using the speed reference?
Issue:
Is it standard practice to use the speed reference to start and stop the drive while keeping the run command activated?

Product Line:
Altivar drives

Environment:
All models and serial numbers

Cause:
N/A

Resolution:
No, it is not recommended to start and stop using the speed reference. When the run command is activated, the output transistors are biased ON. This can increase the opportunity for voltage transients to cause damage. It is recommended to use a switch or relay to deactivate the run command (Digital Input) when the drive is not called to run the motor.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings