How can we help you today?
Why do I get Diagnostic error code 0x000401 on a PM8ECC after I set a new IP address?
Issue:
After setting an IP address in the PM800's PM8ECC there appears a diagnostic error 0x000401.
Product Line:
PM800
PM8ECC
Environment:
PM800
PM8ECC
Cause:
Occurs when the PM8ECC has been programmed with a duplicate IP address.
Resolution:
Change the IP address to an IP that is not being used by another device.
After setting an IP address in the PM800's PM8ECC there appears a diagnostic error 0x000401.
Product Line:
PM800
PM8ECC
Environment:
PM800
PM8ECC
Cause:
Occurs when the PM8ECC has been programmed with a duplicate IP address.
Resolution:
Change the IP address to an IP that is not being used by another device.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.