How can we help you today?

Why am I unable to change Encoder parameters in my ATV71 drive via SoMove?

Issue:
ATV71 drive with encoder card.  When the drive is in I/O profile, SoMove will occasionally not allow parameters related to the encoder to be changed.

Product Line:
Altivar 71 series drives with encoder cards installed.

Environment:
ATV71 drives in I/O profile with encoder cards installed, SoMove V2.0

Cause:
This is an issue with SoMove software that had not previously been reported.

Resolution:
A permanent fix is being worked on to be released in a later update to SoMove.  A temporary work around is to place the drive into Separate Profile, then back into I/O Profile.  This should allow encoder parameter to be changed via SoMove.  Note that the parameters can still be changed via the keypad normally.  This problem only occurs when using SoMove software to program the drive and is a problem with the SoMove software itself, not with the drive.

Schneider Electric UK

Explore more

Range:

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Range:

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.