How can we help you today?

How to start an ATV312 drive using modbus for command?

Issue:
Start an ATV312 using Modbus

Product Line:
Variable Frequency Drives

Environment:
Applies to ATV312

Cause:
Customer is not able to start the drive using Modbus.

Resolution:
Suggested to follow the status chart and send the values to the command word in sequence Hex 6 then 7 then F  to Address 8501 (assuming there is no offset)

flowchart

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.