What is the error in % on class 0.5s and class 1?
For Current transformers the tolerance for each class is as follows:
For class 0.5s, if:
I < 0.01 x In - Percentage ratio error 1.5%
0.01 x In < I < 0.05 x In - Percentage ratio error 0.75%
0.05 x In < I < 0.20 x In - Percentage ratio error 0.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 0.5%
1.00 x In < I < 1.20 x In - Percentage ratio error 0.5%
For class 1, if:
I < 0.05 x In - Percentage ratio error 3%
0.05 x In < I < 0.20 x In - Percentage ratio error 1.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 1.0%
1.00 x In < I < 1.20 x In - Percentage ratio error 1.0%
For more information please refer to the standards IEC 61869-2 (2102)
For class 0.5s, if:
I < 0.01 x In - Percentage ratio error 1.5%
0.01 x In < I < 0.05 x In - Percentage ratio error 0.75%
0.05 x In < I < 0.20 x In - Percentage ratio error 0.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 0.5%
1.00 x In < I < 1.20 x In - Percentage ratio error 0.5%
For class 1, if:
I < 0.05 x In - Percentage ratio error 3%
0.05 x In < I < 0.20 x In - Percentage ratio error 1.5%
0.20 x In < I < 1.00 x In - Percentage ratio error 1.0%
1.00 x In < I < 1.20 x In - Percentage ratio error 1.0%
For more information please refer to the standards IEC 61869-2 (2102)
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.