Where can I find information on the sw100, sw101, sw102 and sw103 dip switches on the ATV212 drives?

Issue:
ATV212 information from the SW101, SW102, and SW103 dip switches.

Product Line:
Altivar ATV212

Resolution:
There are 5 dip switches on the ATV212 drives
SW101= FM analog output U= voltage output I = current output
SW102= Sink Source switch
SW103= Term Switch. Selection of communication terminal resistor. When SW103 is set to Term, internal 120 Ohm termination resistor is connected between A and B terminals.
SW100= VIA= VIA analog input switch (U= voltage input or I= current input)
VIB= VIB analog input switch (0-10-vdc input or PTC input)

screenshot screenshot

screenshot screenshot

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.