How can we help you today?

How do you set the line termination resistor on the ATV212 drive set up for Bacnet protocol?

Issue:
Line termination resistor on the ATV212 drive set up for Bacnet protocol.

Product Line:
Altivar ATV212

Environment:
All

Cause:
Needs to terminate his Bacnet line and wants to know how to set the drive up.

Resolution:
Switch SW103 is the line termination resistance switch to put 120 ohms across the data pins A and B.

Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.