How can we help you today?
Can an ION7330/7350 framework be added to a PM8000 meter
Issue
Can an ION7330/7350 framework be added to a PM8000 meter
Product Line
PM8000 series
Environment
ION Setup
Power Monitoring Expert Designer
Cause
A user wants to copy a framework from an ION7330 meter to PM8000 meter.
Resolution
The default ION73x0 framework will not work in the PM8000. The PM8000 has added some ION modules, as well as removed certain modules (modules removed because new, enhanced modules replaced them). Customized pieces of framework can be added to the PM8000 meter provided the modules are supported on the PM8000.
See this Schneider FAQ "How to Copy and Paste a Framework in Designer" https://www.se.com/us/en/faqs/FA328711/
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.