Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to run an ATV61/71 drive with no load?

Article available in these languages: Spanish

Issue:
How to run an ATV61/71 drive with no load?

Product Line:
Altivar ATV61 ATV71

Environment:
All

Cause:
Needs to test the drive to see if there is a problem with the drive by running the drive open circuit, without the motor connected to it.

Resolution:
Under Drives menu, go to menu 1.8 Fault management.
Find Output Phase Loss, and set to NO

Then go to menu 1.4 Motor Control
Find Motor Control Type, and set to V/F 2pts if it is set to something different.

Note: Make sure to set Output Phase Loss back to yes after testing is done.   Some applications may also require the Motor Control Type to be reset to the previous setting.   Wear necessary protective equipment while testing with OPL set to off, voltage and current will be available at the output terminals of drive

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings