Unity Pro: Instructions for importing a section online using the Wizard.
Issue:
Unity Pro: Instructions for importing a section online using the Wizard
Product Line:
Unity Pro
Resolution:
Message: 'On Line Modification Authorization' indicates that you must build the changes in Offline mode.
The reason for this message is that the Wizard makes several modifications during the import for maximizing the compatibility.
The character set is changed to unicode and leading digits are added to the variables.
To import a section online you right click on Sections - Choose Import and point to the section - Check Options box 'With wizard...'.
When the import wizard is selected, a confirmation is requested. However, you cannot import a section online with the Wizard unless you set up a Project Setting offline before going online with the project.
If you want to use the Import Section Wizard online, you must do the following before going online to the controller.
-Click on 'Tools\Project Settings'
-Click on 'Variables'.
-Select the checkbox for 'Allow Leading Digits'.
-Click on the down arrow for the 'Character Set'
-Select the 'Unicode'
-Click on 'Apply'.
-Click on 'Yes' to confirm the 'On Line Modification Authorization' message.
-Click on OK to close the 'Project Settings' window.
-Click on \Build\Rebuild All Project'.
-Save the application.
- Connect and to transfer the application to the PLC
- You can then Import the section using the import Wizard.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.