How can I see what kind of fault has tripped GV2ME, GV2P, GV2L and GV2LE motor circuit breakers; Thermal or Magnetic?

Article available in these languages:

  • Korean

Using a GVAM11 combined with a GVAD10xx, it is possible to distinguish between thermal and and magnetic faults.

If there is no fault:

  • GVAM11: contact 05-06 is closed and contact 05-08 is open
  • GVAD10xx: fault contact 97-98 is open
  • No LED is lit

If there is a magnetic fault:

  • GVAM11: contact 05-06 is open and contact 05-08 is closed
  • GVAD10xx: fault contact 97-98 is closed
  • The short-circuit LED is lit, and the trip LED is off


If there is a thermal fault

  • GVAM11: contact 05-06 is closed and contact 05-08 is open
  • GVAD10xx: fault contact 97-98 is closed
  • The trip LED is lit, and the short-circuit LED is off


Wiring Diagram

Test for correct operation

The instantaneous auxiliary contact test is performed by creating a state of transition of the handle actuator between the de-energised position and the energised position.
The fault contact test is performed by pressing the test button when the handle actuator is in the closed position.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center