How can we help you today?
How can I choose the electrical protection of a PLC?
The circuit-breaker must protect the PLC against high inrush currents on power-up and overloads during nominal operation.
- Magnetic protection (inrush current on starting) is provided by a iC60 Curve D circuit-breaker (see below for the choice of rating).
- Thermal protection must be provided by a thermal overload relay rated at the transformer secondary In.
Selection of circuit-breaker:
In the power supply module characteristics, it is the It current on activation that interests us (for each type of power supply).
Example:
BMXCPS2000 ( see product data sheet )
It = 0.06 A at 240 VAC [Inom = 0.31 A]
The important operating point is located 10 ms into the circuit-breaker trip curve.
At 10 ms, we have an inrush = It/10 ms = 0.06/0.01 --> 6.0 A per power supply.
For product characteristics regarding your PLC. please visit our website www.se.com/uk where you can find product Data sheets.
For further information about the protection that Schneider Electric can offer , please access to the next link:
Electrical Protection | Electrical Protection and Control | Schneider Electric UK
Contactors and Protection Relays | Schneider Electric UK
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.