Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How is the Start/Stop circuit wired for the ATS48 soft starter?
Issue:
Where do you wire the start run circuit for the ATS48 soft starter?

Product Line:
Altistart 48 ATS48

Environment:
All

Cause:
NA

Resolution:
For 2-wire control , jumper the RUN and STOP terminals and wire a run contact between the 24V and RUN terminals.
2 wire control
For 3-wire control, wire a N/C stop contact between 24V and STOP and wire a N/O start contact between 24V and RUN.
3 wire control

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings